S/FTP CAT7A
S/FTP CAT7A
S/FTP CAT7A

Review

Description

S/FTP Shielded CAT7A Twisted Pair Installation Cable

Standard:

IEC/ISO 61156-5

ANSI/TIA568C.2

ISO/IEC 11801

Application:

Suitable for structured premises cabling.

For transmission of digital and analogue voice and data signals.

ISDN,Ethernet 10Base-T, Fast Ethernet 100 Base-T.Gigabit Ethernet 1000 Base-t,10G Base-T. 

TokenRing4/16Mbit/s,TPPMD/TP/DDI125Mbit/s,ATM155Mbit/s(IEEE 802.5)




                                                                                 Specifications
Conductor
Structure
Single Core/Stranad Core
Material
Copper
Wire gauge
23AWG
Dielectric
Dielectric
1.40±0.10mm
Material
Physical Foam PE
Shielding material 
Each Pair Sinlge-sided Alumunum Foil/Braiding Wire
Rip Wire
150D Polyester straight-dragged
Jacket
Sheath material
PVC/Flexi PVC/PUR
Cable O.D
8.2±0.3mm
Jacket tjickness
0.65±0.1mm
Print words
OEM
Package
Drum
Installation temperature
0℃~+60℃
Use and storage temperature
-20℃~+60℃
Net weight
18.3kg/305m

Electrical properties
Characteristic Impedance
4-100MHZ
100±15Ω
100-250MHZ
100±22Ω
250-1000MHZ
100±25Ω
Single conductor DC resistance
≤9.5Ω/100M
The line-to internal DC resistance is unbalanced
≤2.0%
Dielectric strength between DC 
conductors
1000V,1min No breakdown
Propagation delay difference 
≤45ns/100m
Propagation delay
≤536ns/100m
Operation capacitance
≤5.6nF/100m
Rated transmission rate (NVP)
78%
Insulation resistance
≥5000MΩ km DC(100-500)V
Performance Parameter
Frequency
Attenuation
(dB/100m)
(Max)
Return
loss(dB)
(Min)
Next(dB)
(Min)
PSNEXT(dB)
(Min)
ACR-F
(dB/100m)
(Min)
PSACR-F
(dB/100m)
(Min)
(MH)z
(dB)
(dB/100m)
(ns/100m)
(ns/100m)
(dB)
(dB)
4
3.7
23
78
75
78
75
8
5.2
24.5
78
75
77
74
16
7.3
25
78
75
71
68
20
8.2
25
78
75
69
66
31.25
10.3
23.6
78
75
65
62
62.5
14.6
21.5
78
75
59
56
100
18.5
20.1
75
72
55
52
200
26.5
18
71
68
49
46
250
29.7
17.3
69
66
47
44
500
42.8
17.3
65
62
41
38
600
47.1
17.3
64
61
40
37
700
51.1
16.6
63
60
38
35
1000
61.9
15.1
60
57
35
32